Orlando Home Inspection - 50 Most Common Problem with New Homes
   
50 Most Common Problems with New Homes: 11 thru 20

11.   Some of the exterior cement siding has recessed nails. Recessed nails lose their holding strength in fiber cement siding. All manufacturers require the nails to be flush and not recessed. The recessed nails should be caulked and another flush nail installed next to it.   (1995 CABO 1 & 2 Family Dwelling Code, Section 108.1) 

12.   Exterior openings in the structure are not sealed. This will allow air leaks into the structure. All exterior joints in the building envelope, that are sources of air leaks, shall be caulked, gasketed, weather-stripped or otherwise sealed in an approved manner. (1995 CABO 1 & 2 Family Dwelling Code, Section 1004.1)

13.   Chimney height is not tall enough. This could be a potential fire hazard. All chimneys shall extend 2' higher than any portion of roof within 10' and at least 3' higher than the roof penetration. (1995 CABO 1 & 2 Family Dwelling Code, Section 1004.1)

14.   Roof shingles have toe board nail holes present. Toe boards are walk boards the roofers use. Any holes in the shingles could turn into a roof leak. All shingles with holes should be replaced or sealed with a sealant that will last as long as the shingles. Roof shingles shall provide a barrier against the weather to protect its supporting elements and structure beneath. (1995 CABO 1 & 2 Family Dwelling Code, Section 901.2)

15.   Roof shingles are missing roofing felt at the sheathing along the eaves. This protects the roof sheathing. Slopes of 4 in 12 or greater, one layer of felt is required over all of the roof decking. (1995 CABO 1 & 2 Family Dwelling Code, Section 902.2)

16.   Step flashing is missing at sloped vertical walls. Some of the roof flashing at the vertical walls is continuous flashing. Flashing prevents water from entering at the intersection of the wall and the roof. Continuous flashing was used successfully for many years. However, step flashing is a far superior method of flashing and is required for all roofing. Flashing against a vertical sidewall shall be the step-flashing method. (1995 CABO 1 & 2 Family Dwelling Code, Section 903.6)

17.   Deck footings are smaller than the minimum allowable size of 12" x 12". See Figure 403.1a, note #5 and Table 502.3.3b. Footings shall comply with Section 403. (1995 CABO 1 & 2 Family Dwelling Code, Section 325.5)

18.   Deck footings do not extend 12" below grade. All footings must be below the frost line. In no case shall exterior footings be less than 12 inches below grade. (1995 CABO 1 & 2 Family Dwelling Code, Figure 403.1a, note #1)

19.   Deck stair handrail is not the correct size. Handrails that are 2x4 or larger are too large to be used for handrails since they cannot be gripped. Handrails shall have either a circular cross section with a diameter of 1 1/4" to 2", or a noncircular crosssection with a perimeter dimension of at least 4" but not more than 6 1/4" and a largest cross section dimension not exceeding 2 3/4". Edges shall have a minimum radius of 1/8". (1995 CABO 1 & 2 Family Dwelling Code, Section 315.2)

20.   Exterior deck is missing properly installed flashing. Flashing prevents water from entering behind the deck and into the structure. Flashing is required where decks attach to a wall or floor assembly of wood frame construction. Exterior balconies, decks and porches shall be flashed in accordance with section 703.8. (1995 CABO 1 & 2 Family Dwelling Code, Section 325.2.1)

View Additional Problems